(Kurva LV Mag-freq)
Riżultati tat-Test
Substazzjonament: q | Post: |
Trans. #: a | Trans. Mfr: |
Trans. Mudell: | Data ta' Mfg: |
Nru tas-serje: | Qawwa Kklassifikata: |
Vultaġġ Stmat: | Fażijiet: Fażi Unika |
Frekwenza: 50Hz | Grupp ta' Vetturi: |
Imp(%): | Tkessiħ: Tkessiħ taż-Żejt |
Temp.: 25dC | %RH: |
Temp.: 25dC | Taptap Pos.: |
Konnessjoni Pos.: Bushing | Tip ta' Test: Test ta' Rutina |
Ittestjat minn: | Kumpannija: |
Standard: DL/T911-2016 | |
Figura 1 Kurvi tat-Test #1:HV_OA_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 144420 #2:HV_OB_00,Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 144539 #3:HV_OC_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 144704 #4:MV_OA_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 153545 #5:MV_OB_00, Air Temp.:25dC, Temp taż-Żejt.:25dC, Test ta 'Rutina, 2021-08-31 153814 #6:MV_OC_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 154027 #7:LV1_OA_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 154218 #8:LV1_OB_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 154418 #9:LV1_OC_00, Air Temp.:25dC, Oil Temp.:25dC, Test ta 'Rutina, 2021-08-31 154608 | |
Analiżi tad-Dejta
R_lf 1-100kHz | R_mf 100-600kHz | R_hf 600-1000kHz | R_wf 10-1000kHz | Riżultat (Referenza) | |
R1-2 | 5.01 | 5.28 | 4.11 | 5.36 | Normali |
R2-3 | 4.73 | 5.11 | 4.24 | 5.21 | Normali |
R1-3 | 4.79 | 5.14 | 4.04 | 5.26 | Normali |
R4-5 | 4.59 | 5.33 | 4.11 | 5.31 | Normali |
R5-6 | 4.31 | 5.26 | 4.43 | 5.29 | Normali |
R6-4 | 4.39 | 5.04 | 4.12 | 5.17 | Normali |
R7-8 | 4.52 | 5.29 | 4.17 | 5.32 | Normali |
R8-9 | 4.43 | 5.19 | 4.02 | 5.17 | Normali |
R9-7 | 4.78 | 5.13 | 4.35 | 5.25 | Normali |
3.Konklużjoni u Approvazzjoni
Konklużjoni tat-test:
| |||
Verifikatur: | Approva: | ||